Brands |
N/A Beacon™ RKI Instruments |
Approvals |
N/A Canadian Standards Association (CSA) Certified to CSA C22.2 No. 61010-1-12 and Underwriters' Laboratories (UL) 61010-1 |
Material Warranty |
N/A 1 year |
Workmanship Warranty |
N/A 1 year |
Industry Standards/Certifications |
N/A CCSAUS Underwriter Laboratories (UL) Registered Firm International Organization for Standardization (ISO) 9001: 10000363 |
Enclosure |
N/A NEMA 4X Fiberglass / Polyester with Lexan Window for Indoor and Outdoor Locations |
Conduit Connection |
N/A 3/4" NPT Conduit Hubs, 4 Provided, for Sensor, Power, and Relay Wiring |
Wiring Termination |
N/A Screw Type Terminal Block, 14 Gauge Max |
N/A Strobe Light, and Battery Backup Assembly |
|
Controls |
N/A
Display PCB Control Switches:
|
Universal Alternating Current (AC) Voltage |
N/A 115 V220 V |
Nominal Direct Current (DC) Voltage |
N/A 24 V |
Note for Power |
N/A Battery Backup Option Available |
Operating Temperature |
N/A -20 to 50 ºC-4 to 122 ºF |
Storage Temperature |
N/A -40 to 70 ºC-40 to 158 ºF |
Enclosure Rating |
N/A NEMA-4X Enclosure, Chemical and Weather Resistant. Suitable for Indoor and Outdoor Installations. |
Direct Wired Sensors |
N/A LEL, Oxygen, Carbon Dioxide, and Toxic Gas Sensors. Remote Amplifier Not Required for Less Than 500 Feet. |
4 to 20 Milliampere (mA) Sensors |
N/A Accepts any 4 to 20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4 to 20 mA signals. Wiring distances up to 8000 feet. |
Sampling Methods |
N/A Diffusion and Sample Draw Heads Available |
Relays |
N/A Two flexible, programmable Form-C (C, NO, NC) relays per channel, plus five common relays (Fail, Alarm-1, Alarm-2, Alarm-3, Alarm-Any). Common relays may optionally be assigned to function as additional channel alarm relays, providing for up to three alarm relays per channel. 10 A contact rating, 250 V. |
4 to 20 Milliampere (mA) Output |
N/A Signal Output, 4 to 20 mA (Maximum Load Impedance 500 ohms), per Channel. |
RS-485 |
N/A Modbus Format RS-485 Serial Output of All Channel Data, Including Gas Reading and Alarm Status. |
Display |
N/A Four Line Organic Light-Emitting Diodes (OLED) Display |
Audible |
N/A Built-in Audible Alarm, 94 dB, Mounted on Enclosure Coded Output: Pulsing = Gas Alarm, Steady = Fail. |
Visual |
N/A
|
N/A
|
N/A
|
N/A
Each channel has up to three fully configurable alarm points. A built-in silence able audible alarm alerts you to alarm conditions. Each channel also has two dedicated fully configurable relays and there is a bank of common relays as well. The common relays can optionally be configured as additional relays allowing up to 3 alarm relays per channel. Each channel provides a 4 to 20 mA output signal. A digital Modbus interface for remote logging of data via a Modbus network is standard. A Min-Max feature retains high & low peak readings for review at any time. |