Brands |
N/A Beacon™ RKI Instruments |
Approvals |
N/A Canadian Standards Association (CSA) Certified to CSA C22.2 No. 61010-1-04 and Underwriters' Laboratories (UL) 61010-1 |
Material Warranty |
N/A 1 year |
Workmanship Warranty |
N/A 1 year |
Industry Standards/Certifications |
N/A CCSAUS |
Enclosure |
N/A Wall Mounting Gray Fiberglass with Hinged Cover |
Conduit Connection |
N/A 3/4" NPT Conduit Hubs, 2 Provided. 1 for Sensor Wiring and 1 for Power and Relay Wiring. |
Wiring Termination |
N/A Screw Type Terminal Block, 14 Gauge Maximum |
Controls |
N/A 3 Internal Push Buttons for Setup, Programming, and Calibration. 1 External push button for alarm reset. |
Universal Alternating Current (AC) Voltage |
N/A 115 V220 V |
Nominal Direct Current (DC) Voltage |
N/A 24 V |
Note for Power |
N/A Battery Backup Option Available |
Operating Temperature |
N/A -20 to 50 ºC-4 to 122 ºF |
Storage Temperature |
N/A -20 to 70 ºC-4 to 158 ºF |
Enclosure Rating |
N/A NEMA-4X Enclosure, Chemical, and Weather Resistant. Suitable for Indoor and Outdoor Installations. |
Direct Wired Sensors |
N/A LEL, Oxygen, Carbon Dioxide, and Toxic Gas Sensors. Amplifier not Required for Less Than 500 Feet |
4 to 20 Milliampere (mA) Sensors |
N/A Accepts any 4 to 20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4 to 20 mA signals. Wiring distances up to 8,000 feet |
Sampling Methods |
N/A Diffusion and Sample Draw Heads Available. |
Relays |
N/A Three relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarms and 1 trouble relay. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay |
4 to 20 Milliampere (mA) Output |
N/A Signal Output, 4 to 20 mA (Maximum Load Impedance 500 ohms), per Channel. |
24 Direct Current (DC) Voltage Output |
N/A 24 VDC (400 mA max) Output Provided to Operate Sample Drawing Adapters or Other Accessories. |
Display |
N/A 2 x 8 Alphanumeric Display with Backlighting |
Audible |
N/A Built-in Audible Alarm, 94 dB, Mounted on Enclosure Coded Output: Pulsing = Gas Alarm, Steady = Fail |
Visual |
N/A 3 Light Emitting Diode (LED) on the Front Cover for Alarm Status Indication, and Malfunction. Optional Top-mount Strobe. |
N/A
|
N/A
|
N/A